Electrical

100A → 200A service upgrade. Standard LED-dimmable switches. Outlets replaced. EV conduit stub-out. Cat6 drops. Lighting plan TBD per room.

Locked

  • Service upgrade: 100A → 200A (required for heat pump + induction + future EV)
  • Outlets: replace every receptacle house-wide; GFCI/AFCI per code, tamper-resistant, weather-resistant in wet zones
  • Switches: LED-compatible dimmable standard switches (Lutron Diva or equivalent); skip smart-switch ecosystem
  • EV charger: conduit + 50A breaker stub-out now; charger deferred (see budget for full / skip alts)
  • Ethernet: 2–3 hardwired Cat6 drops to ceilings (main central, upper central, possibly modem area)
  • Existing baseboard circuits removed (replaced by heat pump)

Open / to price

  • Confirm 100A is current service (check main breaker label)
  • Sub-panel needed (upper floor / kitchen) or single panel sufficient?
  • Panel location — keep or relocate?
  • Number of Cat6 drops — 2 / 3 / more
  • Lighting plan per room — recessed cans, pendants, sconces, task; switching layout (worth a session per room)
  • Kitchen outlet strategy — backsplash vs. pop-up; USB-C in island
  • Exterior lighting — entry, deck, condenser pad, pathway
  • Hot water heater electrical (if HPWH alt)
  • Hot tub disconnect — being removed (see Rec room)
  • Sauna heater electrical — typ. 6–9 kW = 30–40A 240V; coord. Sauna

Cost overview options

EV charger (radio)
Option Cost Notes
Conduit + 50A breaker stub-out (chosen) $300–800 Cheapest insurance
Full Level 2 charger installed $1.5–3k All-in upfront
Retrofit after walls closed $2.5–4k+ What we're avoiding
Skip $0 Foregone
Cat6 drops (radio)
Option Cost
3 drops (main + upper + modem) $300–600
2 drops (main + upper) $200–400
Skip $0

See main budget to toggle.

Refs

Load math for 200A
Load Approx. amps
High-velocity heat pump ~30A
Induction range ~40A
Heated floor (main bath) ~5A
Future EV charger ~50A
Hot water (if HPWH alt) ~30–60A
Lighting + outlets + balance balance

100A trips on concurrent load. 200A leaves headroom for EV. 400A would only matter with EV + spa + workshop stacking.